Features:
- C13 style sockets
- LCD indicated unit power
- 19'' mounting
- 3 metre input lead terminated with 16 Amp IEC 60309 plug
- High quality,cold rolled steel housing
- Up to 12 sockets per unit
- 250 volt AC, 50/60Hz Rating
- External earth facility
- CE compliant, ROHS complaint
Specification:
Socket Type: IEC 60320 C13
Input Plug: IEC 60309 (16 Amp) *2 pcs
Power Lead Length: 3 Metres *2.5mm² PVC * 2 pcs
Maximum amperage: 16A
LCD display: real time current; A source / B source voltage
Switch Time: A source cut off - 7ms is needed, A source arc extinguished - 6 to 10 ms, B source start to work - 7ms is needed, Total no more than 25 ms
Using the ''Relay'' to switch from source A To source B
Rs232 port: Mintor via Computer
Product Overview
The STS power distribution units are designed for installation and use within 19" networking cabinets and enclosures.
It has dual 16A input power cords supplying power to the connected load.
The button "preference" is to chose "source A" or "source B" work preferentially.
If the primary power source becomes unavailable, the rack STS will seamlessly source power from the secondary source without interrupting critical loads.
Sample Show
2 x C14 power input
4 x triple IEC C13 power outlet
# Package