A sealed IP66 steel enclosure for outdoor installation of DIN-rail and non-19" telecom equipment. It has a lockable waterproof door, a removable mounting panel and bottom cable entry. The standard size is 300 × 200 × 400 mm; other sizes are listed below or made to order.
Protection (IP66)
- Dust-tight: complete protection against dust, oil and other non-corrosive material
- Complete protection against contact with the equipment inside
- Water projected in powerful jets (12.5 mm nozzle) from any direction has no harmful effect
- Third-party tested
Features
- Welded frame body
- Lockable full metal door with waterproof lock and earthing cable to the earthing bar
- Removable inner door, adjustable for depth
- Removable galvanised or powder-coated mounting panel for equipment
- Rear wall mounting with anchoring bolts, sealed with waterproof sealant
- Bottom cable entry sealed with a metal flange
- Earthing and panel-mounting hardware supplied
- Available wall-mounted, free-standing, trough-mounted or pole-mounted
- Options: lighting, smoke alarm, temperature sensor; cooling by fan, air conditioner or heat exchanger with set points to order
- Made to order with cutouts, insulation, hinges, latches or locks; logo silk-screening, anodising or engraving available
Construction
- Body and door: 16 or 18 gauge (1.0/1.2 mm) cold-rolled steel
- Inner door: sheet steel
- Inner panel: 14 or 16 gauge galvanised sheet
Specifications
| Standard size | 300 × 200 × 400 mm (W × D × H); custom sizes available |
|---|---|
| Protection | IP66 (IP65 and IP55 also available) |
| Material | SPCC cold-rolled steel, galvanised (zinc-plated) sheet or stainless steel |
| Thickness | Mounting panel 2.0 mm; other parts 1.20 mm (1.2, 1.5 and 2.0 mm available) |
| Fabrication | Laser cutting, CNC punching, CNC bending, welding, stamping |
| Finish | Degreased, acid pickled, rust-proofed and phosphated, rinsed in pure water and electrostatic powder coated. Also available: painting, plasma electrostatic painting, hot-dip galvanising, polishing, brushing, cataphoresis |
| Colour | RAL7035 or custom |
| Operating temperature | -40°C ~ +60°C |
| Relative humidity | ≤95% (at 40°C) |
| Atmospheric pressure | 70 kPa ~ 106 kPa |
| Operating wavelengths | 850 nm, 1310 nm, 1550 nm |
| Dielectric strength | ≥3000 V DC for 1 minute between the high-voltage protective earth and the frame, with no breakdown or flashover |
| Insulation resistance | ≥20,000 MΩ at 500 V DC between the high-voltage protective earth and the frame (also quoted as >1000 MΩ at 500 V DC) |
| Surface load | Each surface withstands a vertical pressure over 980 N |
| Open door load | Outer edge of the open door withstands a vertical pressure over 200 N |
| Cable fixing | Withstands 1000 N axial tension and three cycles of ±90° twist |
| Mechanical durability | No damage to connectors or adaptors after 500 matings |
| Water test | Water spray at 10 mm/min and 0.2 MPa for 30 min with no leakage inside |
| Installation | Complete module; overhead, in-pipe or direct-buried cable routes |
| Standards | ANSI/EIA RS-310-D, IEC297-2, DIN41491 Part 1, DIN41494 Part 7, GB/T3047.2-92, ETSI |
| Certification | CE, RoHS, SGS, ISO, REACH |
| Drawing files | SolidWorks, AutoCAD, PDF |
Sizes
| Item Number | Wide(MM) | Deep(MM) | High(MM) |
|---|---|---|---|
| 323 | 300 | 200 | 300 |
| 324 | 300 | 200 | 400 |
| 326 | 300 | 200 | 600 |
| 423 | 400 | 200 | 300 |
| 424 | 400 | 200 | 400 |
| 426 | 400 | 200 | 600 |
| 626 | 600 | 200 | 600 |
| 628 | 600 | 200 | 800 |
| xxx | customized | customized | customized |
Installation and use
- Protect the cabinet from mechanical damage and improper handling, and use it only for its intended purpose
- Do not exceed the maximum recommended load; spread the load evenly
- Do not install equipment that could affect the operation of the cabinet or the installed equipment, and do not modify the cabinet
- On a floor, stand the cabinet on a flat surface and take up any unevenness with the levelling feet
- Seal unused cable openings with a brush blanking panel or plastic frame (available separately) to keep dust out
- All parts are recyclable; dispose of the cabinet according to the relevant regulations