Skip to Content

IP66 outdoor cabinet, wall-mount


SupplyFactory order
Minimum order10 units
Lead time25 days + freight
FreightArranged to your site

Made to order by our manufacturing partners. Samples can be arranged before a volume order.

A sealed IP66 steel enclosure for outdoor installation of DIN-rail and non-19" telecom equipment. It has a lockable waterproof door, a removable mounting panel and bottom cable entry. The standard size is 300 × 200 × 400 mm; other sizes are listed below or made to order.

Protection (IP66)
  • Dust-tight: complete protection against dust, oil and other non-corrosive material
  • Complete protection against contact with the equipment inside
  • Water projected in powerful jets (12.5 mm nozzle) from any direction has no harmful effect
  • Third-party tested
Features
  • Welded frame body
  • Lockable full metal door with waterproof lock and earthing cable to the earthing bar
  • Removable inner door, adjustable for depth
  • Removable galvanised or powder-coated mounting panel for equipment
  • Rear wall mounting with anchoring bolts, sealed with waterproof sealant
  • Bottom cable entry sealed with a metal flange
  • Earthing and panel-mounting hardware supplied
  • Available wall-mounted, free-standing, trough-mounted or pole-mounted
  • Options: lighting, smoke alarm, temperature sensor; cooling by fan, air conditioner or heat exchanger with set points to order
  • Made to order with cutouts, insulation, hinges, latches or locks; logo silk-screening, anodising or engraving available
Construction
  • Body and door: 16 or 18 gauge (1.0/1.2 mm) cold-rolled steel
  • Inner door: sheet steel
  • Inner panel: 14 or 16 gauge galvanised sheet
Specifications
Standard size300 × 200 × 400 mm (W × D × H); custom sizes available
ProtectionIP66 (IP65 and IP55 also available)
MaterialSPCC cold-rolled steel, galvanised (zinc-plated) sheet or stainless steel
ThicknessMounting panel 2.0 mm; other parts 1.20 mm (1.2, 1.5 and 2.0 mm available)
FabricationLaser cutting, CNC punching, CNC bending, welding, stamping
FinishDegreased, acid pickled, rust-proofed and phosphated, rinsed in pure water and electrostatic powder coated. Also available: painting, plasma electrostatic painting, hot-dip galvanising, polishing, brushing, cataphoresis
ColourRAL7035 or custom
Operating temperature-40°C ~ +60°C
Relative humidity≤95% (at 40°C)
Atmospheric pressure70 kPa ~ 106 kPa
Operating wavelengths850 nm, 1310 nm, 1550 nm
Dielectric strength≥3000 V DC for 1 minute between the high-voltage protective earth and the frame, with no breakdown or flashover
Insulation resistance≥20,000 MΩ at 500 V DC between the high-voltage protective earth and the frame (also quoted as >1000 MΩ at 500 V DC)
Surface loadEach surface withstands a vertical pressure over 980 N
Open door loadOuter edge of the open door withstands a vertical pressure over 200 N
Cable fixingWithstands 1000 N axial tension and three cycles of ±90° twist
Mechanical durabilityNo damage to connectors or adaptors after 500 matings
Water testWater spray at 10 mm/min and 0.2 MPa for 30 min with no leakage inside
InstallationComplete module; overhead, in-pipe or direct-buried cable routes
StandardsANSI/EIA RS-310-D, IEC297-2, DIN41491 Part 1, DIN41494 Part 7, GB/T3047.2-92, ETSI
CertificationCE, RoHS, SGS, ISO, REACH
Drawing filesSolidWorks, AutoCAD, PDF
Sizes
Item NumberWide(MM)Deep(MM)High(MM)
323300200300
324300200400
326300200600
423400200300
424400200400
426400200600
626600200600
628600200800
xxxcustomizedcustomizedcustomized
Installation and use
  • Protect the cabinet from mechanical damage and improper handling, and use it only for its intended purpose
  • Do not exceed the maximum recommended load; spread the load evenly
  • Do not install equipment that could affect the operation of the cabinet or the installed equipment, and do not modify the cabinet
  • On a floor, stand the cabinet on a flat surface and take up any unevenness with the levelling feet
  • Seal unused cable openings with a brush blanking panel or plastic frame (available separately) to keep dust out
  • All parts are recyclable; dispose of the cabinet according to the relevant regulations